Blue Line™ D1-P TriTech® Detector Installation Instructions

Bosch Security Systems

Blue Line™ is a trademark of Bosch Security Systems in the United States and other countries.

TriTech® and Pet Friendly® are registered trademarks of Bosch Security Systems in the United States.

1 Specifications

Microwave

  • Blue Line D1-P1-F1 10.525 GHz
  • Blue Line D1-P1-F2 10.588 GHz
  • Blue Line D1-P1-F3 9.9 GHz

Input Power

  • 10 VDC to 14 VDC

Current Draw

  • 15 mA @ 12 VDC standby
  • Alarm current 22 mA

Standby Power

  • No internal standby battery. For UL Listed Product Installations, 4 hours (20 mAh) standby power must be provided by the control unit or by a UL Listed burglary power supply.

Relay

  • Solid State Supervised Form “A” normally-closed (NC) rated for 125 mA at 28 VDC, 3 W.

Tamper

  • NC (with cover on) contacts rated at 28 VDC, 125 mA maximum. Connect tamper circuit to a 24-hour protection circuit.

Digital Alarm Output

  • 5 V normally, ground during alarm

Supervision

  • The unit is tested every 3 h. If the microwave fails, the PIR continues to operate.

Temperature

  • -20°F to +120°F (-29°C to +49°C)
  • For UL Listed installations, the temperature range is +32°F to +120°F (0°C to +49°C)

Humidity

  • 0 to 95% non-condensing

Dimensions

  • 5.2 in. x 2.4 in. x 1.9 in. (13.2 cm x 6.1 cm x 4.8 cm)

Pet Immunity

  • Bosch Security Systems Pet Friendly® Blue Line D1-P TriTech Detector does not detect one to two pets up to 100 lb (45 kg) total or numerous rodents. The pet immunity feature was not tested by UL.

Options

  • B335 Low Profile Swivel Mount Bracket, B328 Gimbal Mount Bracket, and B338 Ceiling Bracket. These brackets can reduce the detector’s range and increase the dead zone area.
  • Note: You cannot use a camera with the B338 Ceiling Mount Bracket.

Compliance

  • This device complies with Part 15 of the FCC Rules and with RSS-210 of Industry and Science Cananda. Operation is subject to two conditions:
    1. This device cannot cause harmful interference.
    2. This device must accept any interference, including interference that might cause undesired operation.
  • Changes or modifications not expressly approved by Bosch Security Systems can void the user’s authority to operate the equipment.
  • Use only a Listed limited-power source.
  • Connect all wiring to a safety extra-low voltage (SELV) circuit only.

2 Installation Considerations

  • Not suitable for outdoor use (2-1).
  • Never install the detector where the PIR or microwave is in constant alarm (LED on). The LED is off when properly installed.
  • Point away from outside traffic. Microwave energy passes through non-metallic walls.
  • Point away from direct and indirect sunlight (2-2).
  • Point away from glass or other objects that rapidly change temperatures (2-3, 2-4, and 2-5).
  • Point away from rotating machines (fans) (2-6).

3 Coverage Patterns

  • Top view (3-1)
  • Side view (3-2)
  • Optional look-down (3-3)
  • Microwave coverage
  • PIR coverage

4 Mounting Considerations

  1. Insert a flat head screwdriver in slot (4-1) and lift to open cover.
  2. Select a mounting location. Mount the sensor where an intruder is most likely to cross the coverage pattern (4-2).
  3. Mount the detector 7.5 ft to 9 ft (2.25 m to 2.7 m) above the floor (4-3).
  4. Pet mounting recommendations:
    • Range of pet immunity (4-4).
    • Do not point the detector where pets can climb (4-5).

5 Mounting

  1. Optional: Mount the detector temporarily by peeling the blue tape off the back of the base to expose the adhesive. Do not use where adhesive can damage the wall.
  2. Mount the base using one of these options:
    • for surface or corner mounting, use the appropriate mounting holes (5-1) and the screws provided.
    • use the optional B335 Bracket here (5-2).
    • use the optional B328 Bracket here (5-3).
    • use the optional 338 Bracket here (5-4)
  3. Note: Do not over tighten the mounting screws. The cover might not attach correctly.
  4. For the wall tamper function, insert the two pan head screws through the wall tamper knockouts (5-6). If needed, use the anchors provided to secure the unit.
  5. Wire the detector base. Thread the wires through the appropriate diameter wire knockouts on the detector base (5-7) or on the removable top insert (5-8).
  6. When wiring from below, thread wiring through these wire knockouts that are perpendicular to the base (5-9).
  7. Use the cable ties (5-10) for strain relief.

6 Terminal Block Wiring

Terminal block (5-11) wiring:

  • 6 VDC to 15 VDC (6-1)
  • NC alarm contacts (6-2)
  • NC tamper contacts (6-3)
  • Digital alarm output (6-4)

7 LED Operation

  1. Select LED (7-1) operation:
    • Jumper position for LED on (7-2)
    • Jumper position for LED off (7-3)
  2. Turn the microwave range to minimum (7-4). Perform a Walk Test to set the appropriate range for your installation.
  3. Non-pet installations only: Create a look-down zone directly below the detector by removing the tape covering the lens (7-6) on the inside of the front cover.
  4. Note: You cannot cover the look-down zone once the tape is removed.
  5. Replace the cover.
  6. To lock the cover (optional):
    1. Press the top of the cover tab (7-7) with your finger to lift the lower edge.
    2. Lift the lower end of cover tab with your finger (7-8) to open it.
    3. Insert a flat head screwdriver in the slot (7-9) in the cover tab opening and turn it 180° to lock the cover. Indicator points down (7-10).

8 LED Display

The Blue Line D1-P has blue, yellow, and green LEDs that light for various alarm and supervision trouble conditions.

  • LED off.
  • LED on.
  • LED sequence.
  • Walk Test disabled.
  • Walk Test enabled, power up.
  • Walk Test enabled, dual alarm.
  • Walk Test enabled, microwave alarm.
  • Walk Test enabled, PIR alarm.
  • Walk Test enabled, no activity.

9 Walk Test

Note: Ensure the LED jumper is set to on (7-2).

Note: To avoid false alarms, set the microwave range (7-4) to its minimum setting before starting the Walk Test.

  • Microwave coverage
  • PIR coverage
  1. Wait at least 2 minutes after power up to start the Walk Test.
    • The blue, yellow, and green LEDs light in sequence until the detector stabilizes and no movement is detected for 2 seconds.
    • The LEDs do not light when there is no motion.
  2. Enable the Walk Test from the keypad.
  3. Observe the LED as you walk to the farthest edge of the pattern. Walk closer to the detector by crossing the pattern (8-1).
    • The green LED lights, identifying the PIR pattern edge.
    • The yellow LED lights, identifying the microwave pattern edge.
    • The blue LED indicates alarms in both the microwave and PIR mode.
  4. Repeat Step 3 from the opposite side.
  5. If the required range is not achieved, increase the microwave adjustment (7-5) by turning it counter-clockwise slightly.
    • Repeat the walk test and adjustments until you reach the farthest edge of coverage needed.