Blue Line P1 - Passive Infrared Detector Installation Instructions
1. Specifications
- Input Power: 9 VDC to 15 VDC
- Current Draw: 10 mA @ 12 VDC standby, 18 mA alarm current
- Standby Power: No internal standby battery. For UL Listed product installations, 4 hours (40 mAh) standby power must be provided by the control unit or by a UL Listed burglary power supply.
- Solid State Relay: Supervised Form "A" normally-closed (NC) rated for 125 mA at 28 VDC, 3 W
- Tamper: NC (with cover on) contacts rated at 28 VDC, 125 mA maximum. Connect tamper circuit to a 24-hour protection circuit.
- Digital Alarm Output: 5 V normally, grounded during alarm
- Temperature: -20°F to +120°F (-29°C to +49°C). For UL Listed installations, the temperature range is +32°F to +120°F (0°C to +49°C)
- Humidity: 0 to 95% non-condensing
- Dimensions: 4.2 in. x 2.4 in. x 1.9 in. (10,7 cm x 6,1 cm x 4,8 cm)
- Options: B335 Low Profile Swivel Mount Bracket, B328 Gimbal Mount Bracket, and B338 Ceiling Bracket. These brackets can reduce the detector's range and increase the dead zone area. Note: You cannot use a camera with the B338 Ceiling Mount Bracket.
1 Use only a Listed limited-power source.
2 Connect all wiring to a safety extra-low voltage (SELV) circuit only.
2. Installation Considerations
- Not suitable for outdoor use (2-1).
- Never install the detector where the passive infrared (PIR) is in constant alarm (LED on). The LED is off when properly installed.
- Point away from direct and indirect sunlight (2-2).
- Point away from glass or other objects that rapidly change temperatures (2-3, 2-4, and 2-5).
- Do not install this detector where pets are present (2-6).
3. Coverage Patterns
- Top view (3-1)
- Side view (3-2)
- Optional look-down (3-3)
4. Mounting
- Insert a flat head screwdriver in slot (4-1) and lift to open cover.
- Select a mounting location. Mount the sensor where an intruder is most likely to cross the coverage pattern (4-2).
- Mount the detector 7.5 ft to 9 ft (2,25 m to 2,7 m) above the floor (4-3).
- Mount the base using one of these options:
- for surface or corner mounting, use the appropriate mounting holes (4-4) and the two flat head screws and anchors provided.
- use the optional B335 Bracket here (4-5).
- use the optional B328 Bracket here (4-6).
- use the optional B338 Bracket here (4-7).
- For the wall tamper function, insert the two pan head screws through the wall tamper knockouts (4-8). If needed, use the anchors provided to secure the screws.
- Wire the detector base. Thread the wires through the appropriate diameter wire knockouts on the detector base (4-9) or on the removable top insert (4-10).
- When wiring from below, thread wiring through these wire knockouts that are perpendicular to the base (4-11).
- Use the cable ties (4-12) for strain relief.
5. Terminal Block Wiring
Terminal block (4-13) wiring:
- 9 VDC to 15 VDC (5-1)
- NC alarm contacts (5-2)
- NC tamper contacts (5-3)
- Digital alarm output (5-4)
6. LED Operation
- Select LED (6-1) operation:
- Jumper position for LED on (6-2)
- Jumper position for LED off (6-3)
- Optional: Create a look-down zone directly below the detector by removing the tape covering the lens (6-4) on the inside of the front cover. Note: You cannot cover the look-down zone once the tape is removed.
- Replace the cover.
- To lock the cover (optional):
- Press the top of the cover tab (6-5) with your finger to lift the lower edge.
- Lift the lower end of cover tab with your finger (6-6) to open it.
- Insert a flat head screwdriver in the slot (6-7) in the cover tab opening and turn it 180° to lock the cover. Indicator points down (6-8).
7. Walk Test
Note: Ensure the LED jumper is set to on (6-2).
- Wait at least 2 minutes after power up to start the Walk Test.
The LED lights for 1 to 2 minutes until the detector stabilizes and no movement is detected for 2 seconds. The LED does not light when there is no motion.
- Watch the LED as you walk to the farthest edge of the pattern. Walk closer to the detector by crossing the pattern. The LED lights at the outside edge of the coverage range.